2020 Tech Report May-June
Task # 2.b.: Performing Float Switch Testing on Liquid Make-Up Systems With- out a Drain Valve
ACTION
COMMENT
12.
Re-start the associated compressors one at a time to prevent the suction pressure from falling too quickly. Verify that the suction piping is clear and free of liquid. Verify all portions of the refrigeration sys- tem are operational. Re-start associated compressors that were turned off in steps above. Repeat this Maintenance Procedure for each float switch that has a liquid make- up system without a drain valve configu- ration, starting with Task # 1 “Preparing for Float Switch Testing.” If this is the last float switch to be tested today, cleanup your work area. Secure your equipment and prepare to document your work. Continue to Task # 3 “Documenting Float Switch Testing.”
Refer to the corresponding SOP for each com- pressor.
13.
14.
Refer to the corresponding SOP for each com- pressor.
15.
See Task # 1 of this Maintenance Procedure.
16.
See Task # 3 of this Maintenance Procedure.
RETA TECHNICAL REPORT PAGE 18
Made with FlippingBook - professional solution for displaying marketing and sales documents online