Microsoft Word - SOP - Hands-On Sessions
P-015
Maintenance Procedure Non-Standard Oil Draining
Page 9 of 20
2.b. Oil Draining Configuration “B”
STEP/ACTION
COMMENT
15. Document amount of oil drained in log.
Waste oil is left outside the engine room to gas off for 2-4 hours, then measured and the quantity recorded in the Master Maintenance Log. Then the oil can be disposed of properly. Please see your supervisor if you have questions concerning proper disposal. Log entries must contain the name of a person making the entry as well as the time, date, and pertinent details of the entry. Be specific! See Task #3.b. of this Maintenance Procedure.
16. Log oil draining of < equipment drained > into the Master Maintenance Log and Daily Rounds Log.
17. Go to Task #3.b. “Returning a Configuration “B” to Normal Operation.”
2.c. Oil draining Configuration “C”
STEP/ACTION
COMMENT
1. Confirm that Task 1 “Preparing for Non-Standard Oil Draining” has been completed. If not completed, do so now before continuing with this Maintenance Procedure.
NOTE: If the possibility exists that the conditions may have been altered after preparation of the plan, you must repeat the “Preparing for Non-Standard Oil Draining” procedure. CAUTION: This particular configuration is potentially hazardous. A Management of Change shall be initiated to add a positive shut-off valve prior to spring return oil drain valve.
Revision 1, November 1, 2023
This Copy Printed: November 1, 2023
MP-015 Non-Standard Oil Draining.doc Last Reviewed: October 30, 2023