catwalk, but the forced draft condenser is several feet higher than the catwalk. While IIAR2, specifically mentions the condenser catwalks as an example of a working platform, some regulatory officials consider the top of the condenser to be the working platform height. When the water distribution nozzles are services, the mist eliminators are removed and boards are typically laid across the top of the condenser, thus creating a “working platform.” Keep this in mind when installing or upgrading relief headers. The cost of an extra few feet of pipe is small compared to regulatory fines. Another requirement for discharge height is found in Section 15.5.1.3 of IIAR2. 15.5.1.3 The discharge termination from piping relieving to atmosphere shall not be less than 7.25 ft (2.2 m) above a roof Where a higher adjacent roof level is within 20 ft (6.1 m) horizontal distance from the relief discharge, the discharge tem1ination shall not be less than 7 .25 ft (2.2 m) above the height of the higher adjacent roof. Pictures 7 & 8 show some instances where this requirement is not met. In Picture 7, the downward discharge is less than 2 feet above the roof. In Picture 8, the relief discharge is only a few feet above grade, and is well below the adjacent roofline. Moving on to maintenance of the relief valves. IIAR6-2019 states: 13.1.1 All pressure relief valves (PRYs) that relieve to atmosphere shall be recertified or replaced on the 5-year time-based frequency. While there are many ways to track the replacement dates, the most commonly used method is to punch the appropriate month and year on the attached install/replace tag on the SRV when it is installed. Picture 9: No Punches Note that IIAR6 does address a lack of punches:

Picture 7

Picture 6

Picture 8

Picture 9: No Punches

13.1.1.1 The service life of the PRV shall not exceed 5 years of service after it is installed on the system. 13.1.1.1.1 Where the PRV Date Tag was not punched during installation, and PRV records do not indicate the installation date, then the worst-case installation date on the PRY Date Tag is assumed and shall be punched upon inspection. However, as in the case of Picture 10 , if no tags are on the relief valve and there is no additional record of installation, then the PRV must be assumed to be overdue for replacement.

Picture 10: No Tags

Bill Lape is Project Director for SCS Engineers. Bill is a Certified Industrial Refrigeration Operator, a Certified Refrigeration Service Technician, and a member of the National Board of Directors of the Refrigerating Engineers and Technicians Association.

22 RETA.com

Made with FlippingBook - professional solution for displaying marketing and sales documents online